The Lenze control system with EtherCAT

Interaction of the components

Explanation of the transitions during system start
While a state is passed through, different tests are carried out (e.g. it is tested whether the

physical topology complies with the configuration). If the tests are successful, the system

automatically changes to the next state.

Detailed information about the possible bus states and the required commissioning steps

can be found here:



Commissioning of the system

( 42)

Status

What happens?

What is tested?

PLC

EtherCAT

Origin

Unknown

The system starts.

Is a master XML file available?

Origin

Init

EtherCAT is initialised.

Master XML file is imported.

Bus scan is executed

Does the imported master XML

comply with the result of the bus

scan?

Origin

Pre-Operational

EtherCAT is active.

SDO communication is possible.

Is an executable boot project

available?

Running

Safe-Operational The PLC program is being loaded.

The PLC is running.

The inputs are transferred, the

outputs are still in a safe state.

Are all inputs ok and initialised?

Running

Operational

The system is running.