1 ethercat bus not in operation, Control technology | ethercat communication manual – Lenze EtherCAT control technology User Manual

Page 32

Advertising
background image

Control technology | EtherCAT communication manual

The Lenze control system with EtherCAT

Interaction of the components

32

L

DMS 3.1 EN 01/2011 TD17

4.4.2

Communication between engineering PC and field devices

For commissioning of the field devices, an online connection is required between the

engineering PC and the corresponding field device. Depending on the state of the EtherCAT

bus, there are two options:



EtherCAT bus not in operation

( 32)



EtherCAT bus in operation (gateway function)

( 33)

4.4.2.1

EtherCAT bus not in operation
You can communicate serially or via CANopen.

Condition:

 Serial communication:

– You require the E94AZCUS diagnostic adapter.
– Field device and engineering PC (USB interface) must be connected via the diagnostic

adapter.

 Communication via CANopen

– You required the EMF2177IB USB system bus adapter .
– Field devices and the engineering PC are connected via the system bus adapter -

either via a point-to-point connection or via the bus system.

Advantage:

 Quick option of communication without commissioning of the EtherCAT bus.

Disadvantage:

 You require additional hardware.

Tip!
As soon as the fieldbus has been commissioned and at least achieved the Pre-

Operational state, this communication path comes second. We recommend to

commission the EtherCAT bus as soon as possible to be able to use the gateway

function.