12 logbook message: "cyclic command wkc error, Logbook message: "cyclic command wkc error, Logbook message: "cyclic command – Lenze EtherCAT control technology User Manual

Page 156: Wkc error ..." ( 156), Control technology | ethercat communication manual

Advertising
background image

Control technology | EtherCAT communication manual

Diagnostics

Error scenarios

156

L

DMS 3.1 EN 01/2011 TD17

11.6.12

Logbook message: "Cyclic command WKC error ..."

The "Cyclic command WKC error" message is entered cyclically every 5 seconds into the

logbook of the industrial PC until the error is not active anymore.

Error notifications in the »PLC Designer«
In the "ETHERCATMaster Status" visualisation template of the »PLC Designer«, the

following error notifications are highlighted in red (fault):

...

xxxxx DD-MM-YYYY hh:mm:ss
EtherCAT Master Stack

SLV: Cyclic command WKC error on LWR - Address: 0x10000 -
WKC act/set=2/7
Communication on bus systems
Error

...

Causes

Remedies

The EtherCAT slave sync managers do not receive any

messages and a time-out expires.

Example: An unplugged bus cable between two

EtherCAT nodes has been replugged. Afterwards,

however, neither the SMC_ResetAxisGroup function

block nor a

Bus restart ( 139)

have been executed.

1.Stopping the PLC program: Execute the menu

command OnlineStop.

2.Plug in the bus cable.

3.Execute the SMC_ResetAxisGroup function block or a

Bus restart ( 139)

.

Advertising