3 setting up a dc synchronisation – Lenze EtherCAT control technology User Manual
Page 60
![background image](/manuals/565926/60/background.png)
Control technology | EtherCAT communication manual
Commissioning of the system
Detailed commissioning steps
60
L
DMS 3.1 EN 01/2011 TD17
7.2.7.3
Setting up a DC synchronisation
Motion applications always require DC synchronisation.
DC synchronisation can also be used for Logic applications.
To be able to use the DC function, the first slave connected to the EtherCAT master (IPC)
must be DC-master-capable.
The first EtherCAT node connected to the IPC is the DC master which provides the other
bus nodes (including the IPC) with the exact time.
In the arrangement of the slaves following then, DC-capable and non-DC-capable
devices can be mixed.
For field devices with communication modules (e.g. Servo Drives 9400 or Inverter
Drives 8400), a synchronisation source must be selected via code C01120. If the DC
setting and the selection of the sync source differ from each other (C01120 = MXI1 and
"DC nused"), the devices cannot be set to the Operational state.
For Servo Drives 9400, code C13892/C14892 = 1 must be set (process data mode =
"deterministic mode").
Note!
The manual configuration of the slave DC features requires a detailed
knowledge of EtherCAT and the field device. Thus, DC settings should only be
made by experts.
A faulty configuration can cause maloperation and negative influences on the
system.