Control technology | EtherCAT communication manual

Commissioning of the system

Detailed commissioning steps

How to set the DC synchronisation:

1. Configure the synchronisation of the EtherCAT slaves via distributed clocks (DC).

• Set the Distributed clocks (DC) cycle time at the EtherCAT Master:

• The DC cycle time to be set in the »EtherCAT Configurator« must be identical to

the EtherCAT task cycle time set in the »PLC Designer«.

• Select the cycle times, according to the technical data, between 1 and 10 ms.
• The (basic) cycle time set here is valid for all Logic and Motion nodes

synchronised by distributed clocks.