Parameter reference

Interface parameters of the MC-ETC communication card in slot 1

C1096/18

C1096/19

AL status codes

Parameter | Name:

C1096/18 | ECAT Enable Linkmessages

Data type: UNSIGNED_8

Index: 23479.18

d

=

0x5BB7.0x12

h

Debug parameter:

If the parameter is set to the value "1", all state changes of the slave are output as diagnostic frames via the Ethernet

interface. In the event of a fault, this enables error diagnosing by means of a Wireshark recording.

(»Wireshark«: Program for analysing network communication links)

• Value "0": No link messages

• Value "1": Enable link messages
Setting range

(min. value | unit | max. value)

Lenze setting

0

1 0

;

Read access ; Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C1096/19 | ECAT Error Code

Data type: UNSIGNED_32

Index: 23479.19

d

=

0x5BB7.0x13

h

Display of the AL status code (slave register "0x0134 : 0x0135")

;

Read access … Write access … CINH … PLC STOP … No transfer

Code (hex)

Description

Current state or state

change

Resulting state

0x0000

No error

Any

Current state

0x0001

Unspecified error

Any

Any + E

0x0011

Invalid requested state

IS, IO, PO, OB,

SB, PB

Current state + E

0x0012

Unknown requested state

Any

Current state + E

0x0013

Bootstrap not supported

IB

I + E

0x0014

No valid firmware

IP

I + E

0x0015

Invalid mailbox configuration

IB

I + E

0x0016

Invalid mailbox configuration

IP

I + E

0x0017

Invalid sync manager configuration

PS, SO

Current state + E

0x0018

No valid inputs available

O, S, PS

P + E

0x0019

No valid outputs

O, SO

S + E

0x001A

Synchronisation error

O, SO

S + E

0x001B

Sync manager watchdog

O, S

S + E

0x001C

Invalid sync manager types

O, S

S + E

PS

P + E

0x001D

Invalid output configuration

O, S

S + E

PS

P + E

0x001E

Invalid input configuration

O, S, PS

P + E

0x001F

Invalid watchdog configuration

O, S, PS

P + E

Legend:
I: Init (initialisation)
B: Bootstrap (not supported)
P: Pre-Operational
S: Safe Operational
O: Operational
E: Error Flag