Control technology | EtherCAT communication manual

Commissioning of the system

Typical commissioning scenarios

7.4.3

Updating the PLC application while the EtherCAT configuration remains unchanged

Initial situation:

 PLC and EtherCAT are running.

– PLC state: Running
– EtherCAT state: Operational

How to update the PLC application:

1. Stop the PLC.
2. Execute "Reset (Original)".

• The PLC is reset, the PLC application is deleted.

3. The system starts up.

• You have to manually load and start the PLC application.