Control technology | EtherCAT communication manual

Synchronisation with "Distributed clocks"

Adjusting task cycle time and DC cycle time

38

L

DMS 3.1 EN 01/2011 TD17

6.2

Adjusting task cycle time and DC cycle time

The industrial PC is the fieldbus master in the EtherCAT network. The clock pulse of the

EtherCAT bus system is determined by the cycle time of the task which is assigned to the

drives (slaves) in the »PLC Designer«.
The task settings in the »PLC Designer« only support integer millisecond cycles and the

smallest possible bus cycle is 1 millisecond. This cycle time can be defined via the task

configuration of the »PLC Designer«.

Note!

• The DC cycle time to be set in the »EtherCAT Configurator« must comply with

EtherCAT task cycle time set in the »PLC Designer«.

• Select the cycle times, according to the technical data, between 1 and 10 ms.