3 communication times and drive-specific data, Communication times and drive-specific data, Control technology | ethercat communication manual – Lenze EtherCAT control technology User Manual

Page 35

Advertising
background image

DMS 3.1 EN 01/2011 TD17

L

35

Control technology | EtherCAT communication manual

Technical data

Communication times and drive-specific data

5.3

Communication times and drive-specific data

Field

Values

User data per frame

1344 bytes

Process data words (PZD) for Servo

Drives 9400 HighLine

max. 32 words (64 bytes)

Parameter data (SDO) transfer

Max. 128 bytes

Permissible EtherCAT cycle times

1 … 10 ms

Max. number of Servo Drives 9400

HighLine per frame

User data of the frame (1344 bytes) divided by the process data length

resulting from setpoints and actual values of the drives:

• for 32 Tx/Rx bytes: 1344 bytes / 64 bytes = 21 drives

• for 16 Tx/Rx bytes: 1344 bytes / 32 bytes = 42 drives

Total signal runtime for a cycle time

of 1ms

Drive



Control



Drive

5 ms

Runtime of the setpoints

Control



Drive

2 ms

Runtime of the actual values

Drive



Control

3ms

Cross communication

Not possible

Cycle synchronisation with locked

PLL (jitter)

+/-1 μs