Control technology | ethercat communication manual – Lenze EtherCAT control technology User Manual

Page 184

Advertising
background image

Control technology | EtherCAT communication manual

Parameter reference

Interface parameters of the MC-ETC communication card in slot 2

184

L

DMS 3.1 EN 01/2011 TD17

C1581/1

C1581/2

C1581/3

Parameter | Name:

C1581/1 | ECAT State Change Command

Data type: UNSIGNED_32

Index: 22994.1

d

=

0x59D2.0x01

h

This code can be used to change the master state.

Note: The parameter should only be set to analyse start problems (e.g. master/bus does not reach the Operational

state). Setting this parameter only sets the state of the master stack. All other nodes remain in their previous states.

Changing the master state via this code may result in an unstable system state.

• A higher bus state than the one initiated by the PLC can never be reached.

• A reload of the master configuration cannot be initiated.

• Loading the PLC program normally stops the bus and sets it to the Pre-Operational state. If this is not possible,

the bus remains in the Unknown or Initialisation state.

• Starting the PLC program normally sets the bus to the Operational state. If this is not possible, the bus remains

in the Pre-Operational or Safe Operational state.

Selection list

(Lenze setting printed in bold)

0 No Operation
1 Init
2 Pre-Operational
4 Safe-Operational
8 Operational

;

Read access ; Write access … CINH … PLC STOP ; No transfer

Parameter | Name:

C1581/2 | ECAT Master State

Data type: UNSIGNED_8

Index: 22994.2

d

=

0x59D2.0x02

h

Display of the current master state
Selection list

(read only)

0 Unknown
1 Init
2 Pre-Operational
3 Bootstrap Mode

Bootstrap Mode is not supported.

4 Safe-Operational
8 Operational

;

Read access … Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C1581/3 | ECAT Master in requested Mode

Data type: UNSIGNED_8

Index: 22994.3

d

=

0x59D2.0x03

h

The state is usually requested by the PLC. For possible requested states see

C1581/1 ( 184)

.

• Value "0": Master is not in the requested state.

• Value "1": Master is in the requested state.
Display range

(min. value | unit | max. value)

0

1

;

Read access … Write access … CINH … PLC STOP … No transfer