Rockwell Automation PLC-5 Fieldbus Solutions for Integrated Architecture User Manual User Manual

Page 107

Advertising
background image

Publication 1757-UM006A-EN-P - May 2002

Configurating the 1757-FIM 4-21

10. To edit a given parameter value, double-click in the desired cell,

or right-click the field and select edit.

The edit field is activated.

11. Enter the desired value and press Enter.

12. Repeat Steps 9, 10, and 11 to edit parameters for your

application, as required.

13. Click File

Build Device Template

From Current Device.

The ProcessLogix device template is built from current data in
the ERDB and a device directory (name pre-defined by the
vendor) is added to the Library tab in Control Builder. If the
device directory already exists, the device is added to the
directory.

14. Click OK to acknowledge the build complete message.

15. Repeat Steps 6 to 14 to make other device templates.

TIP

If your ProcessLogix system architecture includes
multiple clients, the newly created device template
resides only in the database of the Server designated
during FLM login. You must be logged onto the
given Server to access device templates stored in its
ERDB through Control Builder.

Advertising