C - mode change conditions, Reference, Mode change conditions – Rockwell Automation PLC-5 Fieldbus Solutions for Integrated Architecture User Manual User Manual

Page 235: Appendix

Advertising
background image

1

Publication 1757-UM006A-EN-P - May 2002

Appendix

C

Mode Change Conditions

Reference

Input Parameters Status
Attributes, Inputs Values and
Resource States

Mode Parameter - Target Attribute Value

Out of Service
(OOS)

Manual
(MAN)

Automatic
(Auto)

Cascade
(CAS)

Remote
Cascade
(RCAS)

Remote
Output
(ROUT)

All input parameters have Good
Status or Uncertain status with
option set to treat Uncertain as
Good.

OOS

MAN

AUTO

CAS

RCAS

ROUT

Remote cascade in has BAD
status or time-out is detected
and the shed option parameter
value is Normal.

OOS

MAN

AUTO

CAS

Shed to next
permitted or
target mode

(1)

ROUT

Remote cascade in time-out is
detected and the shed option
parameter value is not set to
Normal.

OOS

MAN

AUTO

CAS

Set target and
actual mode as
specified

ROUT

Remote out in has BAD status
or time-out is detected and the
shed option parameter value is
normal.

OOS

MAN

AUTO

CAS

RCAS

Shed to next
permitted or
target mode*

Remote out in time-out is
detected and the shed option
parameter value is not set to
Normal.

OOS

MAN

AUTO

CAS

RCAS

Set target and
actual mode
as specified

Cascade input has a status
attribute of BAD

OOS

MAN

AUTO

Shed to next
permitted
mode

RCAS

ROUT

Target mode is RCAS and
remote cascade in does not
have status of Good -
Initialization Acknowledge; and
actual mode attribute last
execution was not RCAS.

N/A

N/A

N/A

N/A

Actual mode
from last
execution or
AUTO

N/AF

Target mode is ROUT and
remote out in status is not Good
- Initialization Acknowledge;
and actual mode attribute last
execution was not ROUT.

N/A

N/A

N/A

N/A

N/A

Actual mode
from last exe-
cution or MAN