Fieldbus status indications, Fieldbus status indications -18 – Rockwell Automation PLC-5 Fieldbus Solutions for Integrated Architecture User Manual User Manual

Page 62

Advertising
background image

Publication 1757-UM006A-EN-P - May 2002

2-18 Integrating Fieldbus into Rockwell Automation Logix System

The status byte structure consists of a 2-bit quality, most significant bit,
field; a 4-bit substatus field; and a 2-bit limits, least significant bit,
field. The following table provides a breakdown of bit assignments for
general reference. The value of the quality field determines the
applicable substatus field indication.

Fieldbus Status Indications

See Appendix B for list of possible display indications associated with
a given fieldbus status.

Table 2.B Breakdoun of bit assignments

Bit

Quality

Substatus, if Quality field is

Limits

BAD

UNCERTAIN

GOOD
(Non-Cascade)

(1)

GOOD (Cascade)

(1)

0

BAD Data Quality

Non-Specific

Non-Specific

Non-Specific

Non-Specific

No Limits

1

UNCERTAIN Data
Quality

Configuration Error

Last Usable Value

Active Block Alarm

Initialization
Acknow-ledge (IA)

Low Limit

2

GOOD
(Non-Cascade)
Data Quality

Not Connected

Substitute

Active Advisory
Alarm

Initialization Request
(IR)

High Limit

3

GOOD (Cascade)
Data Quality

Device Failure

Initial Value

Active Critical
Alarm

Not Invited (NI)

Constant

4

Sensor Failure

Sensor Conversion
Not Accurate

Unacknow-ledged
Block Alarm

Not Selected (NS)

5

No Communication, with
Last Usable Value

Engineering Unit
Range Violation

Unacknow-ledged
Advisory Alarm

Do Not Select (DNS)

6

No Communication, with
no Last Usable Value

Sub-Normal

Unacknow-leged
Critical Alarm

Local Override (LO)

7

Out-Of-Service

Fault-State Active (FSA)

8

Initiate Fault-State (IFS)

(1)

The Good (non-cascade) substatus is used by output connections for fieldbus blocks such as Analog Input and Discrete Input. The Good (cascade) substatus is used by
output connections for fieldbus blocks such as PID. Both of these substatuses are converted to the single ProcessLogix data quality of Good.