Vxxx blocks, Wxxx blocks – Rockwell Automation PLC-5 Fieldbus Solutions for Integrated Architecture User Manual User Manual

Page 229

Advertising
background image

Publication 1757-UM006A-EN-P - May 2002

Standard Function Block Parameters A-49

Vxxx Blocks

No V parameters

Wxxx Blocks

Table A.130 WRITE_ALM

Table A.131 WRITE_LOCK

Table A.132 WRITE_PRI

Classification

Record

Description

Represents alert that is generated if the write lock is cleared.

FF Data Type

DS-72

Usage

C/Alarm

Length

1, 3

Storage

Dynamic

Remarks

Read Only
The data type describes discrete alarms using the following five elements:

• Unacknowledged
• Alarm State
• Time Stamp
• Subcode
• Value

Classification

Simple Variable

Description

Used to disallow writes from anywhere, except to unlock/clear this parameter,
when it is locked/set. Inputs will continue to read.

FF Data Type

Unsigned 8

Range

1: Unlocked
2: Locked

Usage

C/Contained

Length

1

Valid Views

VIEW_2

Storage

Static

Remarks

The operator can control PROGRAM and LOCAL access to this value.

Classification

Simple Variable

Description

Defines the priority of the alarm generated by clearing the WRITE_LOCK.

FF Data Type

Unsigned 8

Range

0 to 63

Usage

C/Alert Priority