Controlnet discrete input objects, Alarm handling for discrete inputs – Rockwell Automation PLC-5 Fieldbus Solutions for Integrated Architecture User Manual User Manual

Page 170

Advertising
background image

Publication 1757-UM006A-EN-P - May 2002

7-10 Using the 1788-CN2FF, ControlNet-to-FOUNDATION Fieldbus H1 Linking Device

ControlNet Discrete Input Objects

The linking device creates an instance of a ControlNet DI object for
every wired channel in the MDI block instances. Each instance of the
ControlNet DI object has the attributes and access rules shown in
Table 7.C.

All attributes in Table 7.C are created if a standard Fieldbus DI
function block is connected to a channel on an MDI block. Otherwise,
DiscAlmFlag is not created.

Alarm Handling for Discrete Inputs

You can configure Fieldbus DI function blocks to detect and report
alarms.

The process alarm (DISC_ALM) are exposed through the ControlNet
DI object. When you connect a DI function block to an MDI block,
the NI-FBUS Configurator configures the field device to send the
alarm to the linking device.

In Fieldbus terminology, confirming an alarm means that the alarm
has been received by an operator, and acknowledging an alarm
means that the operator has taken the necessary action.

When an alarm condition is detected by a Fieldbus function block, the
alarm is said to be ACTIVE. An active alarm should be Acknowledged
and Confirmed after the condition causing the alarm is corrected.
When the function block detects the alarm condition is no longer
present, the alarm is said to be CLEARED. The CLEARED state must be
Confirmed when it is detected. Users of the LD use the alarm
attributes to process Fieldbus alarms.

Table 7.C ControlNet Discrete Input Object Attributes

Attribute

Number

Name

Type

Access

Initial Value

Remarks

3

Value

Boolean

Get

0

4

CNStatus

Boolean

Get

Bad

ControlNet status. 0-Good; 1-Bad.

150

Ffstatus

uint8

Get

Bad:Out of
Service

Fieldbus status of the value; obtained
from the Fieldbus device.

151

TagDesc

String

Get

As configured

Tag of the Fieldbus function block that is
represented by this object instance.

156

DiscAlmFlag

uint8

Get/Set

0

See Alarm Handling for Discrete Inputs