A-38 Standard Function Block Parameters

Table A.102 ROUT_OUT

Table A.103 RS_STATE

Valid Views

VIEW_3

Storage

Dynamic

Remarks

The data type consists of the value and status of floating point parameters
that are Inputs or Outputs. It uses the following two elements.

• Status
• Value

Classification

Record

Description

Represents block output and status. It serves as input to a host for back calcu-
lation in ROut mode that allows action to be taken under limited conditions or
mode change

FF Data Type

DS-65

Usage

C/Remote-Output Out

Length

5

Valid Views

VIEW_3

Storage

Dynamic

Remarks

Read Only
The data type consists of the value and status of floating point parameters
that are Inputs or Outputs. It uses the following two elements.

• Status
• Value

Classification

Simple Variable

Description

Defines the state of the function block application state machine.

FF Data Type

Unsigned 8

Range

1: Start/Restart
2: Initialization
3: On-Line Linking
4: On-Line
5: Standby
6: Failure

Usage

C/Resource State

Length

1

Valid Views

VIEW_1, VIEW_3

Storage

Dynamic

Remarks

Read Only