Publication 1757-UM006A-EN-P - May 2002

Standard Function Block Parameters A-45

Table A.120 ST_REV

Table A.121 STATUS_OPTS

Table A.122

STATUS_OPTS Bit Selections

Classification

Simple Variable

Description

Defines the revision level of the static data associated with the function block.
The revision value is incremented each time a static parameter value in the
block is changed.

FF Data Type

Unsigned 16

Usage

C/Static Revision

Length

2

Valid Views

VIEW_1, VIEW_2, VIEW_3, VIEW_4

Storage

Static

Remarks

Read Only

Classification

Simple Variable

Description

Defines user-selectable options for the block processing of status.

FF Data Type

Bit String

Usage

C/Contained

Length

2

Valid Views

VIEW_4

Storage

Static

Remarks

See the following Table 3 for a list of the control options by bit and applicable
function block.

Bit Meaning

Function Block

AI

DI

AO DO ML BG CS PD PID RA

0

IFS if BAD IN

X

X

X

X

X

X

1

IFS if BAD CAS_IN

X

X

X

X

X

X

2

Use Uncertain as Good

X

X

X

X

X

X

3

Propogate Failure Forward

X

X

4

Propogate Failure Backward

X

X

X

X

5

Target to Manual if BAD IN

X

X

6

Uncertain if Limited

X

7

BAD if Limited

X

8

Uncertain if Man Mode

X

X

X

X

9

Do not select if not Auto mode

X

X

X

X

10

Do not select if not Cas mode

X

X

11

Reserved

12

Reserved