A-2 Standard Function Block Parameters

Table A.3 ALARM_SUM

Table A.4 ALERT_KEY

Bxxx Blocks

Table A.5 BAL_TIME

Classification

Record

Description

Detects the current alert status, unacknowledged states, and disable states of
the alarms associated with the block

FF Data Type

DS-74

Usage

C/Alarm Summary

Length

8

Valid Views

VIEW_1, VIEW_3

Storage

Dynamic

Remarks

The data type summarizes 16 alerts using the following 4 elements.

•1 Current
•2 Unacknowledged
•3 Unreported
•4 Disabled

Classification

Simple Variable

Description

The identification number of the plant unit. This data may be used in the host
for sorting alarms.

FF Data Type

Unsigned 8

Range

1 to 255

Usage

C/Alert Key

Length

1

Valid Views

VIEW_4

Storage

Static

Remarks

Initial value is 0

Classification

Simple Variable

Description

Specifies the time in seconds for the internal working value of Bias or Ratio to
return to the operator set value.
In PID block, specifies the time constant to be used to move the integral term
to obtain balance, when the output is limited and the mode is Auto, Cas, or
RCas.

FF Data Type

Float

Range

Positive

Usage

C/Contained

Length

4