Integrating Fieldbus into Rockwell Automation Logix System 2-23

Display indications and mode calculation

The fieldbus mode indications for actual mode and composite
actual/target modes will appear in the following formats on Station
displays as shown in Table 2.H.

The block mode calculation of actual mode considers the input
parameter status attributes, input values, and resource state as
represented graphically in Figure 2.8.

Figure 2.8 Block mode calculation summary

See Appendix C for list of conditions, which will change the mode in
order of priority with Good (Non-Cascade) status on input parameter
as the lowest priority.

Table 2.H Fieldbus mode indications

Format

Description

Examples

a

Satisfied in mode a; actual same
as target.

OOS, MAN, AUTO, CAS, RCAS,
ROUT

a (t)

In mode a; not satisfied in higher
target mode t.

MAN (A), CAS (RC), IM (A), LO
(CAS), AUTO (M), CAS (M)

Determine

Host Timeout

Mode

Actual Mode
and Target

Remote Cascade

Remote Out

Shed Option

Cascade

Primary Input

Back Calculation Input

Resource State

Block Specific Inputs

Actual and Target

Mode Calculation

Target Mode