1788-CN2FF Installation Example F-9

4. In Network Address, type in the MAC ID of the 1788-CN2FF.

5. Select the number of ports you are using.

For this example we are only using 1.

6. If your computer is on the same ControlNet and the 1788-CN2FF,

set the Path to 02.

If your computer is on another ControlNet, use the path
suggested by RSLinx. A typical PLX path might be 2 6 1 6 2.

2(1 space)6(1 space)1(1 space)6(1 space)2

7. Leave the Timeout as defaulted.

Click Add.You see:

8. Go to Port Configuration on page F-12.

Finding the Interface Driver Name

If you don’t know the name of your device driver do the following:

1. In RSLinx, select Communication Drivers.:

Communication Drivers