F-52 1788-CN2FF Installation Example

IMPORTANT

At present, Rockwell Automation is not promoting
the use of the distributed control capability of
Fieldbus. That means that all the control is done in
the controller. We are using the Fail-safe processing
capability of the individual Fieldbus devices.

Table F.2 Troubleshooting

If you see:

Do this:

Bad Status, Bad Data Value

Make sure to see that all the Function Blocks and
Transducers are in the proper operating mode.

a function block in OOS mode

OOS = Out Of Service Mode.
In the FFCT window, click on the “T” with the red X
through it.
That will Unhide the Transducer Function Blocks.

a Transducer function block in OOS
mode

Check to see that the Transducer FB is not in the OOS
mode.
If it shows OOS, change it.
All the Function Blocks, including RB, should be in
the Auto mode

Bad Data in the Monitor window

Be sure the RB Function Block is in Auto Mode.