A-16 Standard Function Block Parameters

Table A.43 FF_SCALE

Table A.44 FF_VAL

Table A.45 FIELD_VAL

Classification

Record

Description

Defines the feed-forward input high and low scale values, engineering units
code, and number of digits to the right of the decimal.

FF Data Type

DS-68

Range

0-100 percent

Usage

C/Scaling

Length

11

Valid Views

VIEW_4

Storage

Static

Remarks

The Data type consists of data that describes floating point values for display
purposes. It uses the following four elements.

• Engineering Units at 100 percent
• Engineering Units at 0 percent
• Units Index
• Decimal Point

Classification

Record

Description

Represents the feed-forward value.

FF Data Type

DS-65

Usage

I/Input

Length

5

Valid Views

VIEW_3

Storage

Non-Volatile

Remarks

Read Only
The Data type consists of the value and status of floating point parameters
that are Inputs or Outputs. It uses the following two elements.

• Status
• Value

Classification

Record

Description

Represents the raw value from the field device in percent of transducer span,
with a status reflecting the transducer condition, before signal characteriza-
tion (L_TYPE) or filtering (PV_FTIME).

FF Data Type

DS-65

Usage

C/Contained

Length

5