The Fieldbus Communication Model 1-17

Discrete Input Block

Figure 1.8 Functional Schematic for Discrete Input Function Block

Table 1.H Discrete Input Block Specifications

Description

The Discrete Input function block takes the discrete input data from a selected Transducer block channel and provides
it as an output for other fieldbus function blocks. A functional schematic of the block is shown in Figure 1.8 for
reference.

Function Notes

• Supports Out of Service (OOS), Manual (Man), and Automatic (Auto) modes.

• The FIELD_VAL_D represents the true ON/OFF state of the value from the Transducer, using XD_STATE.

• Use the IO_OPTS Invert selection to do a Boolean NOT function between the field value and the output.

• Use the PV_FTIME to set the time that the input must be in one state before it gets passed to the PV_D.

• The PV_D is always the value that the block places in OUT_D, when the mode is Automatic.

• In Manual mode, if allowed, an operator can write a value to OUT_D.

• The SIMULATE_D parameter is for testing purposes only and always initializes in the disabled state.

Parameters
(see Appendix A
for definitions of
each parameter)

ACK_OPTION
ALARM_SUM
ALERT_KEY
BLOCK_ALM
BLOCK_ERR
CHANNEL
DISC_ALM
DISC_LIM

DISC_PRI
FIELD_VAL_D
GRANT_DENY
IO_OPTS
MODE_BLK
OUT_D
OUT_STATE
PV_D

PV_FTIME
SIMULATE_D
ST_REV
STATUS_OPTS
STRATEGY
TAG_DESC
UPDATE_EVT
XD_STATE

DI

Optional

Invert

Output

OUT_D

Mode

SHED_OPT

FIELD_VAL_D

Transducer

OUT

Simulate

SIMULATE_D

Alarms

DISC

Filter

PV_FTIME

CHANNEL

PV_D