Tag and address assignments

Before a fieldbus device can actively join a network it must be
assigned a name and data link address. Device names are system
specific identifiers called physical device tags (PD_TAG).

The PD_TAGs may be assigned by the vendor or through the System
Management Kernel (SMK), normally in an off-line configuration
environment so devices without tags are kept off the operational
network.

The SMK for devices without tags are set to the Uncommissioned state
and connected to the bus at one of four default device addresses. The
Data Link Layer specifies these default addresses as non-visitor node
addresses. The following figure shows the general allocation of data
link layer addresses to field devices.

Figure 2.10 Summary of address allocations for fieldbus devices

0

10

X

Y

F8

FB FC

FF

Node

Addresses:

Standard, Global,

and Flat Node

Addresses

Usable

Addresses

Usable Addresses

First Unused
Node Address
V(FUN)

Number of

Unused Node

Addresses

V(NUN)

Non-Visitor addresses,

used as default

addresses for devices

requiring address

assignments

Visitor addresses

used for temporary
(handheld) devices

ATTENTION

!

Temporary devices such as handheld interfaces are
not assigned tags or addresses. They join the
network through one of four data link visitor
addresses reserved for them in the data link layer
protocol.