Publication 1757-UM006A-EN-P - May 2002

Using the 1788-CN2FF, ControlNet-to-FOUNDATION Fieldbus H1 Linking Device 7-15

Table 7.E describes the attributes placed into the input and output
assembly for each object type.

MAI Blocks

For each MAI block configured in the linking device beginning with
the lowest numbered module, each channel that is connected to a
Fieldbus function block has attributes 3, 4, and 150 placed into the
required input assembly object. Each MAI channel requires 6 bytes in
the input assembly object.

MAO Blocks

For each MAO block configured in the linking device beginning with
the lowest numbered module, each channel that is connected to a
Fieldbus function block has attributes 3, 4, and 155 placed into the
required output assembly object. Additionally, if your controller
participates in cascade initialization for a specific channel (wiring
BKCAL_OUT from AO), attribute 154 is placed into the required input
assembly. Each MAO channel requires 6 bytes in the output assembly
object and 6 bytes in the input assembly, if cascade initialization is
performed—4 bytes in the input assembly if cascade initialization is
not performed.

Table 7.E Attributes in Input and Output Assemblies

Object Type

Attributes in Input

Assembly

Attributes in Output

Assembly

AI

3, 4, 150

AO
(CAScade initialization)

153, 154

3, 4, 155

AO
(NO CAScade
initialization)

153

3, 4, 155

DI

3, 4, 150

DO
(CAScade initialization)

153, 154

3, 4, 155

DO
(NO CAScade
initialization)

153

3, 4, 155