Publication 1757-UM006A-EN-P - May 2002

4-22 Configurating the 1757-FIM

16. (Optional) Launch Control Builder to confirm that the device

template is listed in the Rockwell Automation directory in the
Library tab.

Making a fieldbus device template from existing definition (.DEF)
files

Use the following procedure to make a device template from
definition files that have been previously saved to a folder on the
Server's hard drive. The default folder location is:
C:\Honeywell\tps50\system\bin\er\ffdevices

.

1. Click Start

Programs

ProcessLogix Engineering Tools

Fieldbus Library Manager.

The Fieldbus Library Manager (FLM) login window opens.

2. In the Server Name field, select the Server where you want the

device template stored.

The device template is stored in the Engineering Repository
Database (ERDB) on the Server.

3. Enter your login password in the Password field.

You need an access level of at least Engineer to make a
template. See your system administrator to get your assigned

ATTENTION

!

Exit the Control Builder application before launching
the Fieldbus Library Manager utility.