Device description infrastructure, Device description infrastructure -28 – Rockwell Automation PLC-5 Fieldbus Solutions for Integrated Architecture User Manual User Manual

Page 42

Advertising
background image

Publication 1757-UM006A-EN-P - May 2002

1-28 The Fieldbus Communication Model

Device Description infrastructure

The Fieldbus Foundation defines a four-level infrastructure for Device
Descriptions for the sake of consistency. See Figure 1.14 for a
graphical representation of the DD infrastructure.

Figure 1.14 Device Descriptions infrastructure.

Levels 1, 2, and 3 are the Device Descriptions that the Fieldbus
Foundation provides on CD-ROM.

Level 1 consists of Universal Parameters that define common
attributes such as Tag, Revision, and Mode. All blocks must include
Universal Parameters.

Level 2 consists of Function Block Parameters that define parameters
for all standard Function Blocks including the standard Resource
Block.

Level 3 consists of Transducer Block Parameters that define
parameters for the standard Transducer block. In some cases, the
Transducer Block specification may add parameters to the standard
Resource Block.

Level 4 is the Manufacturer Specific Parameters that define the
parameters a manufacturer has added to the standard Function Block
and Transducer Block parameters. These added parameters will be
included on the manufacturer's Incremental DD.

RESOURCE

TEMP

FLOW

AI

PID

Resource

Block

Transducer

Block

Function

Block

Level 1:

Universal

Parameters

Level 2:

Function

Block

Parameters

Level 3:

Transducer

Block

Parameters

Level 4:

Manufacturer

Specific

Parameters

Defined by

Fieldbus Foundation

Specification

Defined by

Manufacturer

Advertising