Standard Function Block Parameters A-9

Table A.23

CONTROL_OPTS Bit Selections

Table A.24 CYCLE_SEL

Valid Views

VIEW_4

Storage

Static

Remarks

See the following for a list of the control options by bit and applicable function
block.

Bit

Meaning

Function Block

BG

CS

ML

PD

PID

RA

0

Bypass Enable (LSB)

X

X

1

SP-PV Track in Man

X

X

X

2

SP-PV Track in ROut

X

X

3

SP-PV Track in LO or IMan

X

X

X

4

SP Track retained target

X

X

X

X

5

Direct Acting

X

X

6

Balance Ramp

X

X

X

7

Track Enable

X

X

X

X

X

8

Track in Manual

X

X

X

X

X

9

Use PV for BKCAL_OUT

X

X

X

10

Act on IR

X

X

X

11

Use percent for IN_1

X

X

12

Obey SP limits if Cas or RCas

X

X

X

X

13

No OUT limits in Manual

X

X

X

X

X

X

14

Reserved

15

Reserved

Classification

Simple Variable

Description

A bit string to identify the block execution method selected for this resource.

FF Data Type

Bit String

Usage

C/Contained

Length

2

Valid Views

VIEW_2

Storage

Static

Remarks

Changing this parameter may be fatal to communication.