Appendix

D

Fieldbus Wiring Considerations

The following wiring information is for general purposes only. Refer
to each device’s cooresponding wiring and installation instructions.

Fieldbus Topologies

Figure D.1 illustrates the Spur, Daisy Chain, and Tree type wiring
topologies that can be used to connect fieldbus devices to one
another and a host.

Figure D.1 Overview of fieldbus wiring topologies

FD

FD

FD

FD

FD

FD

T

T

T

T

T

FD

FD

FD

T

Spur Topology
- Requires layout design
- Requires “T” connection
- Allows changing a device
without disturbing other devices

Daisy Chain Topology
- Requires layout design
- Requires terminators
- Difficult to replace one device
without stopping entire Fieldbus
- Difficult to maintain

Branch Topology
- Requires design evaluation
- Requires terminators
- Wiring savings are realized only
in “home run “cable
- Conforms to present practices

HOST

HOST

HOST

Terminator

Terminator

Terminator

Terminator

Terminator

Terminator

Junction Box

Junction Box

Junction Box

Spurs

(Unterminated)

“Home Run” Cable (Trunk)

“Home Run” Cable (Trunk)

I.S.

Barrier

(Optional)

I.S.

Barrier

(Optional)

I.S.

Barrier

(Optional)

PS

PS

PS

TIP

Maximum or acceptable cable distances may be
significantly reduced by using Non-FF spec wire.