Integrating Fieldbus into Rockwell Automation Logix System 2-27

In general, the calculation of actual mode and the use of actual
mode in the algorithm accounts for the status of critical inputs.

4. Calculate output parameters in the backward path.

This phase applies only to output blocks and calculation blocks
designed for use in a cascade path.

Figure 2.9 Algorithm execution phase sequence

TIP

A fieldbus device whose period of function block
execution is an integer factor of the macrocycle of
the link will have a function block execution
schedule prepared that has the optimal shorter cycle.
For example, if the control strategy includes a CM
with a 10 second period for a temperature loop, a
second CM with a 1 second period for a pressure
loop, and a third CM with a 250 millisecond period
for a flow loop, a 1 second macrocycle can be
downloaded to the device that contains functions
blocks used in the 1 second and 250 ms CMs.

Mode

Calculation

Set Point

Calculation

Out

Calculation

Output

Parameters In

Backward Path

Cascade

Remote Cascade

Remote Out

Back Calculation

Primary Input

Block Specific

Parameters

Primary Output

Remote Cascade Out
Back Calculation Out
Remote Out Out

Target

Mode

Actual

Mode

Set Point

PV

SP & OUT

1

2

3

4