Fieldbus analog output or pid data manipulation – Rockwell Automation PLC-5 Fieldbus Solutions for Integrated Architecture User Manual User Manual

Page 55

Advertising
background image

Publication 1757-UM006A-EN-P - May 2002

Integrating Fieldbus into Rockwell Automation Logix System 2-11

Figure 2.5 shows a simplified functional diagram of how the output
from a PID function block in a Control Module that is assigned and
loaded to the CEE in the Control Processor Module (CPM) is
integrated with a cascaded Proportional, Integral, Derivative function
block in a fieldbus compliant device.

Figure 2.5 Integration of fieldbus device PID control with ProcessLogix control
strategy

Fieldbus Analog Output or PID data manipulation

When the OP from the PID function block is wired to the CAS_IN
input for a fieldbus Analog Output or Proportional, Integral,
Derivative function block, the Control Builder automatically creates a
CEE output agent to handle the analog output to the fieldbus block.

CM

CPM/CEE

FIM

Fieldbus
Device

FIM

PID

PV

OP

AIC = Analog Input Channel
BACKCALIN = Back Calculation Input
BKCAL_IN = Back Calculation Input
BKCAL_OUT = Back Calculation Output
CAS_IN = Cascade Input

AIC

DACQ

CAS_IN

RCAS_IN

PID

ROUT_OUT

OUT

CAS_IN

RCAS_IN

RCAS_OUT

BKCAL_OUT

PV

P1

PV

BACKCALIN

Analog

Output

Transducer

OUT

CAS_IN

RCAS_IN

RCAS_OUT

BKCAL_OUT

IN

BKCAL_IN

ROUT_IN

TRK_IN_D

TRK_VAL

FF_VAL

Transducer

Analog

Input

OUT

CEE = Control Execution Environment
CM = Control Module
CPM = Control Processor Module
DACQ = Data Acquistion
FIM = Fieldbus Interface Module

OP = Output
PID = Proportional, Integral, Derivative
PV = Process Variable
RCAS_IN = Remote Cascade Input
RCAS_OUT = Remote Cascade Output
ROUT_OUT = Remote Out Output