A-44 Standard Function Block Parameters

Table A.117 SP_LO_LIM

Table A.118 SP_RATE_DN

Table A.119 SP_RATE-UP

Classification

Simple Variable

Description

Defines the low limit for setpoint entry.

FF Data Type

Float

Range

PV_SCALE +/- 10 percent

Usage

C/Contained

Length

4

Valid Views

VIEW_2

Storage

Static

Remarks

Initial value is zero (0)

Classification

Simple Variable

Description

Defines the downward ramp rate in PV units per second for setpoint changes
to invoke action in the Auto mode.

FF Data Type

Float

Range

Positive

Usage

C/Contained

Length

4

Valid Views

VIEW_4

Storage

Static

Remarks

If the ramp rate is set to zero or the block is not in Auto mode, the setpoint
change is invoked immediately.

Classification

Simple Variable

Description

Defines the upward ramp rate in PV units per second for setpoint changes to
invoke action in the Auto mode.

FF Data Type

Float

Range

Positive

Usage

C/Contained

Length

4

Valid Views

VIEW_4

Storage

Static

Remarks

If the ramp rate is set to zero or the block is not in Auto mode, the setpoint
change is invoked immediately.