Publication 1757-UM006A-EN-P - May 2002

Standard Function Block Parameters A-31

Table A.83 OUT_LO_LIM

Table A.84 OUT_SCALE

Table A.85 OUT_STATE

Classification

Simple Variable

Description

Defines the minimum output value limit in all modes, unless the
CONTROL_OPTS selection No Out limits in Manual is chosen.

FF Data Type

Float

Range

OUT_SCALE +/- 10 percent

Usage

C/Contained

Length

4

Valid Views

VIEW_2

Storage

Static

Remarks

Initial value is 0.

Classification

Record

Description

Defines the high and low scale values, engineering units code, and number of
digits to the right of the decimal point to be used in displaying the OUT param-
eter and parameters that have the same scaling as OUT.

FF Data Type

DS-68

Usage

C/Scaling

Length

11

Valid Views

VIEW_2

Storage

Static

Remarks

The Data type consists of data that describes floating point values for display
purposes. It uses the following four elements.

• Engineering Units at 100 percent
• Engineering Units at 0 percent
• Units Index
• Decimal Point

Classification

Simple Variable

Description

Represents the index to the text describing the states of a discrete output.

FF Data Type

Unsigned 16

Usage

C/Contained

Length

2

Valid Views

VIEW_2

Storage

Static