7-8 Using the 1788-CN2FF, ControlNet-to-FOUNDATION Fieldbus H1 Linking Device

ControlNet AO object has the attributes and access rules shown in
Table 7.B.

The BkCalStatus is created only when the controller is capable of
participating in the CAScade initialization handshake and when the
BKCAL_OUT of the AO block is wired to a BKCAL_INx parameter of
the MAO block.

Only Value, CNStatus, casInstatus, ReadBack, and TagDesc are created
when an MAO is connected to something other than an AO function
block CAS_IN parameter.

Table 7.B ControlNet Analog Output Object Attributes

Attribute

Number

Name

Type

Access

Initial

Value

Remarks

3

Value

Float

Set

0

This is written from the ControlNet
side.

4

CNStatus

Boolean

Set

Bad

ControlNet status. 0-Good; 1-Bad.

11

FailStateValue

Float

Set

0

The linking device writes the value to
the AO block when this attribute is
changed by the controller.

151

TagDesc

String

Get

As
configured

Tag of the Fieldbus function block that
this object instance represents.

152

FailstateTime

Float

Set

0

The linking device writes the value to
the AO block when this attribute is
changed by the controller.

153

ReadBack

Float

Get

0

This represents the BKCAL_OUT value
from the AO block.

154

BkCalStatus

uint8

Get

Bad:Not-
Connected

This represents the status of the
Readback attribute.

155

casInstatus

uint8

Set

Bad:Not-
connected

This represents the status of the
CAS_IN to the AO block.