Configuring DATAACQ block for sample loop

1. In the CM101 chart, double-click the DATAACQ block.

The DATAACQ Block Parameters window opens.

2. In the Name field, type DATAACQ_101.

3. In the Description field, type Level Input Conditioning.

4. In the Eng. Units field, type Percent.

5. Leave the Execution Order in CM field at the default of 20.

TIP

The DATAACQ is a 1757-PLX52 function as well as a
Foundation Fieldbus function, with ControlBuilder
you can mix both in a control strategy.