Publication 1757-UM006A-EN-P - May 2002

1-10 The Fieldbus Communication Model

Table 1.D Analog Input Block Specifications

Description

The AI function block takes the input data from a Transducer block and calculates an output to be fed to other fieldbus
function blocks. A functional schematic of the block is shown in Figure 1.4 for reference.

Function Notes

• Supports Out of Service (OOS), Manual (Man), and Automatic (Auto) modes.

• The XD_SCALE units code must match the channel units code, or the block will remain in OOS mode after being

configured.

• The OUT_SCALE is normally the same as the transducer, unless the L_TYPE is set to Indirect or Ind Sqr Root, then

the OUT_SCALE determines the conversion from FIELD_VAL to the output.

• If the mode is Auto, the PV is the value the block puts in OUT.

• If the mode is Man, an operator can write a value to OUT.

• The SIMULATE parameter is for testing purposes only and always initializes in the disabled state.

Equation Options

FIELD_VAL = 100 x (channel value - EU@0%) / (EU@100% - EU@0%) [XD_SCALE]
Direct: PV = channel value
Indirect : PV = (FIELD_VAL / 100) x (EU@100% - EU@0%) + EU@0% [OUT_SCALE]
Ind Sqr Root: PV = sqrt(FIELD_VAL / 100) x (EU@100% - EU@0%) + EU@0% [OUT_SCALE]

Parameters
(see Appendix A
for definitions of
each parameter)

ACK_OPTION
ALARM_HYS
ALARM_SUM
ALERT_KEY
BLOCK_ALM
BLOCK_ERR
CHANNEL
FIELD_VAL
GRANT_DENY

HI_ALM
HI_HI_ALM
HI_HI_LIM
HI_HI_PRI
HI_LIM
HI_PRI
IO_OPTS
L_TYPE
LO_ALM

LO_LIM
LO_LO_ALM
LO_LO_LIM
LO_LO_PRI
LO_PRI
LOW_CUT
MODE_BLK
OUT
OUT_SCALE

PV
PV_FTIME
SIMULATE
ST_REV
STATUS_OPTS
STRATEGY
TAG_DESC
UPDATE_EVT
XD_SCALE