1

Publication 1757-UM006A-EN-P - May 2002

Appendix

A

Standard Function Block Parameters

(1)

Axxx Blocks

Table A.1 ACK_OPTION

Table A.2 ALARM_HYS

(1)

This reference information is provided by

F

OUNDATION

Fieldbus.

Want more Foundation Fieldbus information?

Visit the Fieldbus Foundation web site at www.fieldbus.org, or the
following address, for more information:

9390 Research Blvd.
Suite II-250
Austin, TX 78759-9780

Classification

Simple Variable

Description

Selects whether alarms associated with the block will be automatically
acknowledged.

FF Data Type

Bit String

Range

1: Unacknowledge

Usage

C/Contained

Length

2

Valid Views

VIEW_4

Storage

Static

Remarks

Initial value is 0

Classification

Simple Variable

Description

Defines the amount of change a PV value must attain within the alarm limits
before the alarm condition clears.

FF Data Type

Float

Range

0 to 50 percent of PV span

Usage

C/Contained

Length

4

Valid Views

VIEW_4

Storage

Static

Remarks

Initial value is 0.5 percent