Publication 1757-UM006A-EN-P - May 2002

The Fieldbus Communication Model 1-25

Ratio Block

Figure 1.13 Functional schematic for Ratio function block.

Table 1.M Ratio Block Specifications

Description

The Ratio function block set point is the ratio of its output to its input. A ratio set point of 0.5 produces an output that
is one half of its input. The input (IN_1) is either a wild flow or the output of a blend-pacing controller. The output can
be used as the set point for a secondary flow controller. An input (IN) from the secondary measurement is used to
calculate the actual ratio, which is displayed as the PV. A functional schematic of the block is shown in Figure 1.13 for
reference.

Function Notes

• Supports Out of Service (OOS), Initialization Manual (IMan), Local Override (LO), Manual (Man), Automatic (Auto),

Cascade (Cas), and Remote Cascade (RCas) modes.

• The input 1 (IN_1) value to be ratioed passes through a filter with a time constant of RA_FTIME. The filtered value

is multiplied by the Set point (SP) and GAIN to become the target output. The GAIN controls the number of zeros in
the SP display.

• The input (IN) value is the actual value of the ratioed variable and it passes through a filter with a time constant of

PV_FTIME. The filtered IN value is divided by the filtered IN_1 value and the GAIN to become the PV. The units of IN
are not PV, but OUT. The units of IN_1 are OUT units divided by PV units.

RA

OUT

Output

OUT_HI_LIM

OUT_LO_LIM

BAL_TIME

OUT

Mode

SHED_OPT

SP

CAS_IN

RCAS_IN

BKCAL_OUT

RCAS_OUT

Setpoint

SP_RATE_DN
SP_RATE_UP

SP_HI_LIM

SP_LO_LIM

Output Track

TRK_SCALE

BKCAL_OUT
RCAS_OUT

CAS_IN

RCAS_IN

BKCAL_IN

TRK_IN_D

TRK_VAL

IN

BKCAL_IN

TRK_VAL

IN_1

TRK_IN_D

Ratio

GAIN

IN

Filter

PV_FTIME

Calc PV

GAIN

Alarm

HI/LO

DEV

PV

IN_1

Filter

RA_FTIME