Publication 1757-UM006A-EN-P - May 2002

A-8 Standard Function Block Parameters

Table A.20 CLR_FSAFE

Table A.21 CONFIRM_TIME

Table A.22 CONTROL_OPTS

Usage

C/Channel

Length

2

Valid Views

VIEW_4

Storage

Static

Remarks

The initial value is 0.

Classification

Simple Variable

Description

Serves as a switch to reset/clear the device failsafe state after the fault con-
dition is cleared.

FF Data Type

Unsigned 8

Range

1: Off
2: Clear

Usage

C/Contained

Length

1

Storage

Dynamic

Remarks

The operator can control PROGRAM or LOCAL access to these values.

Classification

Simple Variable

Description

Defines the time between retries of alert reports.

FF Data Type

Unsigned 32

Range

Positive

Usage

C/Contained

Length

4

Valid Views

VIEW_2

Storage

Static

Remarks

The initial value is 32000 milliseconds.

Classification

Simple Variable

Description

Represents bit string for control options to alter the calculations done in an
applicable function block.

FF Data Type

Bit String

Usage

C/Contained

Length

2