A-18 Standard Function Block Parameters

Table A.48 FREE_TIME

Table A.49 FSAFE_TIME

Table A.50 FSAFE_VAL

Classification

Simple Variable

Description

Identifies the percent of block processing time that is free to process addi-
tional blocks.

FF Data Type

Float

Range

0 - 100 percent

Usage

C/Contained

Length

4

Valid Views

VIEW_1, VIEW_3

Storage

Dynamic

Remarks

Read Only

Classification

Simple Variable

Description

Represents the reaction time in seconds from the detection of a failure at the
output block remote setpoint to the output block action, if the condition still
exists.

FF Data Type

Float

Range

Positive

Usage

C/Contained

Length

4

Valid Views

VIEW_4

Storage

Static

Classification

Simple Variable

Description

Defines the preset analog setpoint to use when a failure occurs. Value is
ignored, if the IO_OPTS Failsafe to value option is false.

FF Data Type

Float

Range

PV_SCALE +/- 10 percent

Usage

C/Contained

Length

4

Valid Views

VIEW_4

Storage

Static