2-32 Integrating Fieldbus into Rockwell Automation Logix System

Notification Scheme

Fieldbus versus ProcessLogix Alarm Priorities

The Fieldbus alarms are closely integrated with the existing
ProcessLogix notification system. The ProcessLogix Server handles
FIM alarms in the same way it handles Control Processor ones. But,
the fieldbus devices themselves own their alarm data and generate the
alarms, clears, and events.

Fieldbus devices use 0 to 15 as numeric priorities for alarm reporting.
ProcessLogix alarms use Journal, Low, High and Urgent as priorities
with a sub-priority of 0 to 255. Table 2.J shows how fieldbus priorities
are mapped to ProcessLogix priorities and severities.

Table 2.J Mapping Fieldbus Priorities to ProcessLogix

Fieldbus Alarm Priority

ProcessLogix Alarm
Priority

ProcessLogix Alarm
Severity

0

(Can never be seen by FIM
or above)

(Can never be seen by FIM
or above)

1

(Can never be seen by FIM
or above)

(Can never be seen by FIM
or above)

2
BLOCK_ERR bit 14
(power-up)
BLOCK_ERR bit 15
(Out-of-Service)

Journal
(Event System Only)

2

3
All other bitstring
indications:
(BLOCK_ERR bits 0-13,
XD_ERROR bits 16-25)

System Level Diagnostic
(High)

2

2 (User selected)

Journal

2

3

Low

3

4

Low

4

5

Low

5

6

Low

6

7

Low

7

8

High

8

9

High

9

10

High

10

11

High

11

12

Urgent

12

13

Urgent

13

14

Urgent

14

15

Urgent

15