A-22 Standard Function Block Parameters

Table A.60 HI_PRI

Ixxx Blocks

Table A.61 IO_OPTS

Table A.62 IO_OPTS Bit Selections

Usage

C/Contained

Length

4

Valid Views

VIEW_4

Storage

Static

Remarks

Initial value is + infinity

Classification

Simple Variable

Description

Defines priority of the high alarm.

FF Data Type

Unsigned 8

Range

0 to 63

Usage

C/Alert Priority

Length

1

Valid Views

VIEW_4

Storage

Static

Remarks

Initial value is 0

Classification

Simple Variable

Description

Identifies user-selectable options for altering the Input and Output block pro-
cessing.

FF Data Type

Bit String

Usage

C/Contained

Length

2

Valid Views

VIEW_4

Storage

Static

Remarks

See the following for a list of the control options by bit and applicable function
block.

Bit

Meaning

Function Block

AI

DI

AO

DO

0

Invert

X

X

1

SP-PV Track in Man

X

X

2

Reserved

3

SP-PV Track in LO or IMan

X

X