D-4 Fieldbus Wiring Considerations

The following table lists limits for some possible fieldbus cable types
listed in the order of usage preference with 1 being preferred.

Another rule of thumb based on Fieldbus Foundation published
guidelines is for the length of spurs and how many devices can be on
various lengths of cable as listed in the following table.

Table D.2 Fieldbus Cable Limits

Preference
Type

Description

Distance
(Meters/Feet)

Resistance
(Ohms per km)

Attenuation
(dB per km)

1

#18 AWG, shielded,
twisted pair

1900/6233

22

3

2

#22 AWG,
multiple-twisted,
pairs with overall
shield

1200/3937

56

5

3

#26 AWG,
multiple-twisted,
pairs without shield

400/1312

132

8

4

#16 AWG, multiple
conductor, no
twisted pairs with
overall shield

200/656

20

8

Table D.3 Number of devices on the fieldbus and maximum spur length

Number of Devices

Maximum Spur Length (Meter/Feet)

1 to 12

120/394 (one device per Spur)

13 to 14

90/295 (one device per Spur)

15 to 18

60/197 (one device per Spur)

19 to 24

30/98 (one device per Spur)

25 to 32

No spurs allowed

ATTENTION

!

The spur length limitations are for spurs with one
device each. Please refer to the Fieldbus Foundation
AG-140 Wiring and Installation Guide for rules on
multiple devices per spur.