Discrete output block, Discrete output block -18 – Rockwell Automation PLC-5 Fieldbus Solutions for Integrated Architecture User Manual User Manual

Page 32

Advertising
background image

Publication 1757-UM006A-EN-P - May 2002

1-18 The Fieldbus Communication Model

Discrete Output Block

Figure 1.9 Functional Schematic for Discrete Output Function Block

Table 1.I Discrete Output Block Specifications

Description

The Discrete Output function block converts the value in SP_D to something useful for the hardware linked to the
CHANNEL selection. A functional schematic of the block is shown in Figure 1.9 for reference.

Function Notes

• Supports Out of Service (OOS), Local Override (LO), Manual (Man), Automatic (Auto), Cascade (Cas), and Remote

Cascade (RCas) modes.

• The Set point (SP_D) supports the full cascade sub-function.

• Use the Cascade mode to transfer the output of another block to the Set point (SP_D) of the DO block.

• Use the IO_OPTS Invert selection to do a Boolean NOT function between the field value and the output.

• Use the IO_OPTS Invert selection to do a Boolean NOT function between the SP_D and the output.

• If the hardware supports a readback value, it is used for READBACK_D, and, after accounting for the IO_OPTS

Invert selection, acts as the PV_D for this block. If this is not supported, READBACK is generated from OUT_D.

• In the Man mode, an operator can force the output, in a programmable logic controller sense. If Man mode is not

permitted, it must be supported as a transition mode for exiting the OOS mode

• The SIMULATE_D parameter is for testing purposes only and always initializes in the disabled state.

Parameters
(see Appendix A
for definitions of
each parameter)

ALERT_KEY
BKCAL_OUT_D
BLOCK_ALM
BLOCK_ERR
CAS_IN_D
CHANNEL
FSAFE_TIME
FSAFE_VAL_D
GRANT_DENY

IO_OPTS
MODE_BLK
OUT_D
PV_D
PV_STATE
RCAS_IN_D
RCAS_OUT_D
READBACK_D
SHED_OPT

ST_REV
STATUS_OPTS
STRATEGY
TAG_DESC
UPDATE_EVT
XD_STATE
SIMULATE_D
SP_D

DO

Transducer

OUT_D

Simulate

SIMULATE_D

Optional

Invert

Optional

Invert

Output

CHANNEL

OUT_D

Mode

SHED_OPT

SP_D

CAS_IN_D

RCAS_IN_D

BKCAL_OUT_D

RCAS_OUT_D

Setpoint

Failsafe

FSAFE_TIME

FSAFE_VAL_D

READBACK_D

PV_D

BKCAL_OUT_D
RCAS_OUT_D

CAS_IN_D

RCAS_IN_D