Proportional/Integral/Derivative Block

Figure 1.12 Functional Schematic for Porportional/Integral/Derivative Function
Block

Table 1.L Proportional/Integral/Derivative Block Specifications

Description

The Proportional/Integral/Derivative function block provides classic three-mode control function for closed-loop
control applications. When the Process Variable deviates from the Set point, the PID function acts upon the error to
move the output in a direction to correct the deviation. PID blocks support cascade applications to compensate for the
difference in process time constants of a primary and secondary process measurement. A functional schematic of the
block is shown in Figure 1.12 for reference.

Function Notes

• Supports Out of Service (OOS), Initialization Manual (IMan), Local Override (LO), Manual (Man), Automatic (Auto),

Cascade (Cas), Remote Cascade (RCas) and Remote-Out (ROut) modes.

• The input (IN) passes through a filter with a time constant (PV_FTIME). The filtered value becomes the Process

Variable (PV) to be used with the Set point (SP) in the block's algorithm. A PID algorithm will not integrate, if the
limit status of the input (IN) is constant.

• The full cascade SP sub-function is used, with rate and absolute limits. Additional control options are available to

have the SP value track the PV value, when the block's actual mode is IMan, LO, Man, or ROut. Limits do not cause
SP-PV tracking.

PID

OUT

Feed Forward

FF_SCALE

FF_GAIN

Output

OUT_HI_LIM

OUT_LO_LIM

OUT

Mode

SHED_OPT

SP

CAS_IN

RCAS_IN

BKCAL_OUT

RCAS_OUT

Setpoint

SP_RATE_DN
SP_RATE_UP

SP_HI_LIM

SP_LO_LIM

Output Track

TRK_SCALE

BKCAL_OUT
RCAS_OUT

CAS_IN

RCAS_IN

BKCAL_IN

TRK_IN_D

TRK_VAL

IN

IN

BKCAL_IN

TRK_VAL

ROUT_IN

TRK_IN_D

FF_VAL

ROUT_OUT

Bypass

BYPASS

Filter

PV_FTIME

Status

BKCAL_HYS

Control

GAIN

RESET

BAL_TIME

RATE

Alarm

HI/LO

DEV

ROUT_IN

ROUT_OUT

PV

FF_VAL