Rockwell Automation PLC-5 Fieldbus Solutions for Integrated Architecture User Manual User Manual

Page 128

Advertising
background image

Publication 1757-UM006A-EN-P - May 2002

4-42 Configurating the 1757-FIM

6. Click the Alarms tab.

7. Enter or select the following values for these Alarm Limits:

Leave all other Alarm Limits at their default values.

8. Click the Block Pins tab.

Alarm Limit

Trip Point

Priority

Severity

PV High High

85

URGENT

15

PV High

70

HIGH

8

PV Low

25

HIGH

8

PV Low Low

15

URGENT

15