S-0-0159 monitoring window – BECKHOFF AX5000 S-IDN Parameters User Manual

Page 117

Advertising
background image

S­IDNs

S­0­0159 Monitoring window

This parameter specifies the maximum permissible deviation between the set and actual positions. If this
difference, which is also referred to as position lag, exceeds the value specified in this parameter, the drive
sets the C1D error bit 11 of S­0­0011.

Attributes

Name

Value

Format

udec

Data length

32

Decimal point

0

Min value

0

Max value

4 294 967 295

Default value

0

Unit

inc

Changeable in EtherCAT state

PreOp, SafeOp, Op

Cyclic transfer

No

Device parameter

No

Related to interface revision

No

Following error monitoring in the AX5000 is only active if the value of S­0­0159 > 0. If the higher­level
controller (NC) monitors the following error (S­0­0189), this parameter can be left at the "default" value of
zero. If the controller does not deal with this task, a value adapted to the application must be specified here.

Note

IDNs involved

S‐0‐0076 [

}

 55]S‐0‐0079 [

}

 57], S‐0‐0189 [

}

 131]

AX5000 ­ IDN­Descriptions

117

Version 3.1