S­IDNs

2

S­IDNs

S­0­0001 Control unit cycle time (TNcyc)

The parameter contains information regarding the time intervals at which the numeric control makes new set
values available.

Attributes

Name

Value

Format

UDEC

Data length

16

Decimal point

0

Min value

125

Max value

20 000

Default value

500

Unit

µs

Changeable in EtherCAT state

PreOp

Cyclic transfer

No

Device parameter

Yes

Related to interface revision

from 200: Interpolation P­0­0556

This parameter must be transferred in PreOp from the master to the slave and is taken into account in the
slave from SafeOp. S­0­0001 must be equal to S­0­0002. 
When using a control mode which contains position control, S­0­0001 must be equal or greater than
P­0­0004. If S­0­0001 is longer than P­0­0004, AX5000 interpolates the missing set values. Interpolation can
be configured in P­0­0556.

Note

IDNs involved

S‐0‐0001 [

}

 9], S‐0‐0002 [

}

 10], P­0­0004, P­0­0556

AX5000 ­ IDN­Descriptions