S-0-0267 password – BECKHOFF AX5000 S-IDN Parameters User Manual
Page 146

SIDNs
S00267 Password
The parameter can be used to enable or disable write protection for passwordprotected IDNs. (The
interface) EtherCAT supports passwords to protect selected parameters.
Attributes
Name
Value
Format
text
Data length
272
Decimal point
0
Min value
Max value
Default value
AX5000
Unit
Changeable in EtherCAT state
PreOp, SafeOp, Op
Cyclic transfer
No
Device parameter
No
Related to interface revision
No
The password write protection is disabled if
• this parameter sent to the drive with the valid password. Parameters with password write protection
can then be changed.
The password write protection is disabled if
• the power supply of the drive is initially interrupted, then restored, or
• if this parameter is sent to the drive without a valid password.
Password levels 1 and 2 exist for AX5000.
Please contact Beckhoff support regarding passwords for password write protection.
Attention
Possible damage and failures caused by changes in passwordlevel 2
Great care must be taken when making changes in IDNs protected in this way, because a
zero offset of the measuring system, for example, could be overwritten irrevocably.
Note
Nested structure
Note the nesting depth and the structure information at the start of the descriptions.
AX5000 IDNDescriptions
146
Version 3.1