S­IDNs

S­0­0909 Dynamic MDT error counter

At each Sync1 time the drive checks whether new valid dynamic MDT data are present. If not, this counter is
incremented. Possible causes of error are late EtherCAT telegrams or incorrectly transferred EtherCAT
telegrams with invalid checksums.

Attributes

Name

Value

Format

UDEC

Data length

16

Decimal point

0

Min value

­

Max value

­

Default value

­

Unit

­

Changeable in EtherCAT state

No

Cyclic transfer

AT

Device parameter

No

Related to interface revision

from 204

This counter should remain static at very low values (1 or 2). Otherwise, the cause should be analyzed.

AX5000 ­ IDN­Descriptions